The BACnet protocol allows building equipment to exchange data in a common format. It thus facilitates the integration of PLCs, sensors, controllers, meters, and monitoring systems into a building management system.
BACnet is primarily used to monitor heating, ventilation, air conditioning, lighting, and energy consumption.
What is the BACnet protocol?
BACnet stands for Building Automation and Control Networks. Developed by ASHRAE, it complies with the ANSI/ASHRAE 135 standard and the international ISO 16484-5 standard.
Its goal is to promote interoperability among a building’s technical systems, even when they are from different manufacturers. The protocol defines how data is organized, identified, and exchanged between devices.
ASHRAE describes BACnet as a protocol designed for the monitoring and control of building systems.
How does BACnet work?
Each BACnet device is represented by a set of objects. These objects correspond to the information that the BMS can read, monitor, or, in some cases, modify.
| BACnet Object | Example of Use |
|---|---|
| Analog Input | Temperature, humidity, or CO₂ concentration |
| Binary Input | Door Condition or Equipment Malfunction |
| Analog Value | Setpoint or calculated value |
| Binary Value | On/Off Control |
| Device | Equipment Identification |
| Schedule | Schedule |
| Trend Log | Price History |
Every object has properties. The property Present_Value, for example, contains the current value of the object. Other properties specify its name, unit, state, or identifier.
Which BACnet services are used in " BMS "?
BACnet services enable devices to interact with one another. The most common ones are:
ReadPropertyto read a propertyWritePropertyto change a value when editing is allowedWho-IsandI-Amto explore the facilitiesSubscribeCOVto receive a notification when a value changes
The COV ( Change of Value) mechanism prevents the need to continuously query a device. Data is transmitted when a significant change is detected, provided that this feature is supported and configured.
BACnet/IP or BACnet MS/TP: What Are the Differences?
The BACnet data model remains the same, but messages can be carried over multiple networks.
| Criterion | BACnet/IP | BACnet MS/TP |
|---|---|---|
| Support | Ethernet/IP Network | RS485 Serial Bus |
| Architecture | Building Computer Network | Chain-type field connection |
| Flow Rate | Higher | More limited |
| Installation | Existing Ethernet Cabling | Dedicated multipair cable |
| Common usage | Supervisors, PLCs, and gateways | Controllers and Field Equipment |
BACnet/IP
BACnet/IP uses the building's Ethernet network. It is suitable for architectures that already have an IP infrastructure and facilitates communication between PLCs, gateways, and supervisory systems.
BACnet MS/TP
BACnet MS/TP operates over an RS-485 connection. Devices are typically connected to the same bus. The cabling, MAC addresses, communication speed, and network termination rules must be followed.
What are the applications of BACnet in a " BMS "?
BACnet can centralize a wide range of technical data:
- Temperature and Humidity
- Indoor air quality
- Condition of Doors and Windows
- Water, gas, or energy consumption
- Technical Defects
- Heating Instructions
- Equipment Orders
- Alarms and Status Changes
BMS can then track the values over time, generate alerts, compare zones, and apply control strategies.
Does BACnet ensure interoperability?
Using the same protocol facilitates interoperability, but does not guarantee that all devices will offer the same features.
Before installing a device, you should check the following:
- Available BACnet objects
- Properties that can be read or written to
- Supported Services
- The equipment's BACnet profile
- The PICS document provided by the manufacturer
- BACnet/IP or BACnet MS/TP compatibility
- The Uniqueness of Device IDs and Network Addresses
Proper preparation of the addressing and point map simplifies the discovery of devices and their integration into the monitoring system.
How do you integrate wireless sensors into a BACnet- BMS ?
BACnet is not a wireless protocol. In a wireless architecture, sensors transmit their data via LoRa or LoRaWAN to a receiver or gateway. This device then converts the data into BACnet objects that can be understood by the BMS.
With a BACnet LoRa Easy receiver
The Enless LoRa Easy BACnet receiver receives data from Enless sensors and automatically converts it into BACnet objects.
It supports:
- BACnet/IP over Ethernet
- BACnet MS/TP via RS-485
- Up to 50 Enless sensors
- Device Mode
- Object Mode
In Device mode, each sensor appears as a separate BACnet device. In Object mode, the receiver serves as the main device and groups together the objects associated with the sensors.
Network settings, Device IDs, and discovery modes are detailed in the RX BACNET GitBook guide.
With a LoRaWAN gateway
Designed for an open LoRaWAN architecture, the Enless LoRaWAN gateway centralizes data from Enless sensors and can also integrate third-party sensors using codecs.
The decoded data is then structured so it can be processed by the BMS. This architecture is suitable for projects requiring more sensors or compatibility with multiple LoRaWAN manufacturers.
Best Practices for BACnet Integration
Before putting the system into service:
- Define an addressing plan
- Assign a unique Device ID to each piece of equipment
- Check the expected items in the BMS
- Choosing Between BACnet/IP and BACnet MS/TP
- Check the RS485 settings in MS/TP
- Test the equipment discovery process
- Check that the units are consistent
- Limit Excessive Queries
- Use the COV when this feature is available
Key Takeaways
BACnet provides a common language for Building Management System (BMS) equipment. It operates based on standardized objects, properties, and services.
When used with a LoRa or LoRaWAN infrastructure, it enables wireless transmission of sensor data to the BMS. The BACnet LoRa Easy receiver and the Enless LoRaWAN gateway provide this bridge between field devices and the monitoring system.
DiscoverEnless Wireless’ BMS s expertise, or contact the Enless team to design the right architecture for your project.
FAQ on the BACnet Protocol
What is the difference between BACnet and Modbus?
Modbus primarily organizes data into registers. BACnet uses objects that include a value, a unit, a status, and other properties. BACnet also provides discovery, alarm, and notification services.
Does BACnet work without an Internet connection?
Yes. A BACnet/IP network can operate entirely on the building's local network. A connection to the cloud or the Internet is not required.
Can a LoRaWAN sensor be connected directly via BACnet?
No. A gateway must receive and decode LoRaWAN data, then make it available to the BMS s in the form of BACnet objects.