Discover the new Enless LoRaWAN thermostatic valve, designed for use with your hydronic radiators. It strictly adheres to the heating setpoints defined by your BMS. Compatible with the 868 MHz LoRaWAN protocol, it not only allows you to adjust the room temperature but, more importantly, to receive your control setpoints remotely.
A thermostatic valve designed for system integrators
The thermostatic valve (part no.: TX VALVE 600-060) was developed with the comfort of BMS integrators in mind. Designed as a single unit, it installs easily on your radiator, and accessing its batteries is very simple—just remove the sleeve. Supplied with 3 AA batteries, this thermostatic valve includes more batteries than most competing LoRaWAN valves, optimizing its operating time and reducing maintenance. Its temperature selector is also clickable, allowing you to activate numerous features (sending test frames, Bluetooth mode, motor calibration, child safety, etc.).
Made in France
The Enless thermostatic valve is entirely manufactured and assembled in France.
LoRaWAN Class A
The Enless thermostatic valve supports the LoRaWAN EU868 protocol in Class A. This means that motor control commands (downlinks) can be received after each uplink message is sent. The valve supports LoRaWAN version V1.0.4 and regional parameters RP002-1.0.3.
It can therefore communicate with any public or private LoRaWAN network.
LoRaWAN Valve Control Modes
The LoRaWAN thermostatic valve can operate in several control modes:
Temperature Mode You send a setpoint temperature to the valve, which uses its built-in temperature sensor and internal algorithm to maintain the desired temperature.
Motor PositionYou send an opening command (in %) to the valve. The internal algorithm is not used; control scenarios are determined by the BMS the valve applies a specific opening percentage.
Summer ModeThe valve is in sleep mode; it sends a status update every day, but its actuator is not controlled and remains in the closed position.
Features supported by the thermostatic head
The thermostatic valve supports the following features:
Open Window Detection If the temperature drops by more than 3°C in less than 15 minutes, a window-open alarm is triggered and the room’s heating is turned off for 30 minutes.
Anti-Seizing System: Regular movement to minimize the risk of seizing. When this feature is enabled, the anti-seizing procedure runs every 28 days. A seizing alarm is triggered if seizing is detected during the procedure.- Setpoint tolerance
Allows the occupant to adjust the setpoint temperature within a defined range around the configured value.
Hydraulic Balancing This feature can only be enabled when the valve is set to "Temperature" control mode. It allows you to set minimum and maximum valve opening and closing percentages to ensure that each radiator receives the water flow it needs.- Display Orientation
Allows you to reverse the default display orientation (180° rotation).
- Child Safety
When this feature is enabled, the knob must be pressed for 10 seconds before any manual operation of the valve can be performed, thereby preventing accidental activation.
To learn more about thermostatic valves, please visit this page.